Elevator Pit Inspection Control: EN 81-20 Stop Device, Hold-to-Run, Pit Lighting and Buffer Requirements

Glossary › Pit Inspection Control

The mandatory control station located in the elevator pit that allows maintenance engineers to drive the elevator at inspection speed from the pit level, with hold-to-run operation, a stop device, and priority over all other controls, enabling safe work on pit-mounted components.

Full Definition
The pit inspection control station (pit inspection box) is required by EN 81-20 for all elevator pits deeper than 0.50 m. Requirements: (1) Stop device — a latching safety switch that cuts power to the drive when actuated; it must be accessible immediately upon entering the pit (within reach of the pit access door/ladder); (2) Inspection control switch — a key-operated or clearly marked two-position switch that transfers control to the pit station; (3) Hold-to-run operation — movement only occurs while the direction button is continuously held; (4) Speed limit — car movement restricted to ≤0.63 m/s (inspection speed) when pit control is active; (5) Priority — pit inspection takes priority over COP and HCP calls; (6) Lighting — EN 81-20 requires permanent pit lighting providing ≥50 lux at pit floor, with a switch at the pit access door and at the pit control station; (7) Pit ladder — a fixed ladder is required for pits deeper than 0.50 m. EN 81-20 also requires: a pit depth of ≥0.50 m (standard) or ≥1.10 m (enhanced, to provide standing space for engineers), a buffer at the bottom of travel for both car and counterweight, and a pit drain or waterproofing for pits prone to flooding. LOLER thorough examinations include the pit safety switch and lighting as mandatory check items.
Back to Glossary
Term
Pit Inspection Control
Usage Area
All elevator pit installations — mandatory pit maintenance control station for safe pit access and component servicing
Explore All Terms
300+ technical definitions for the elevator industry
View All Terms